Electrical Wire Size Calculator

Size electrical wire for any circuit with NEC-based ampacity and voltage-drop checks.

Home NEC 310.16 ampacity Copper & aluminum 3% & 5% voltage drop
Rate this calculator

What wire gauge does your circuit need?

AWG gauge · ampacity · voltage drop · breaker · NEC 310.16

Instructions — Electrical Wire Size Calculator

1

Enter current and one-way length

The current is the continuous amperage the circuit must carry — not the breaker rating. One-way length is the distance from panel to load, not the round-trip. Switch between feet and meters with the unit toggle.

2

Pick voltage, material, and conditions

120 V for U.S. residential branch circuits, 240 V for dryers/ranges, 277/480 V for commercial. Copper handles ~25% more current than aluminum at the same size. Temperature and the number of current-carrying conductors derate ampacity.

3

Read gauge, ampacity, and voltage drop

The result picks the larger of two minimum sizes — the one meeting NEC ampacity and the one keeping voltage drop under 3% (branch) or 5% (feeder). Breaker size is then matched to the wire's termination cap.

Continuous load rule: NEC 210.20(A) requires the breaker (and wire) to handle 125% of any load running 3+ hours. The calculator applies this automatically.
Long runs need upsizing: a 12 AWG / 20 A circuit at 150 ft already drops more than 3% — upsize to 10 AWG even though the ampacity column says 12 AWG is fine.

Formulas

Two checks decide the gauge: ampacity (heat the conductor can dissipate without insulation damage) and voltage drop (how much line resistance steals from the load). The larger of the two sizes wins.

REQUIRED AMPACITY (CONTINUOUS LOAD)
$$ I_{req} = 1.25 \times I_{load} $$
NEC 210.20(A) requires 125% of any load running 3+ hours. A 16 A continuous load needs at least 20 A of ampacity at the conductor and breaker.
DERATED AMPACITY
$$ A_{adj} = A_{base} \times D_T \times D_N \times D_M $$
A_base is the NEC 310.16 table value. D_T is the temperature factor (1.00 at 30 °C, 0.82 at 45 °C, 0.58 above 55 °C). D_N is conductor-count derating (0.80 for 4–6, 0.70 for 7–9). D_M is 1.0 for copper, 0.80 for aluminum.
VOLTAGE DROP (SINGLE-PHASE)
$$ V_D = \frac{2 \times K \times I \times L}{CM} $$
K = 12.9 for copper, 21.2 for aluminum (CM·Ω/ft @ 75 °C). I is current in amps. L is one-way length in feet. CM is the conductor area in circular mils from the AWG table.
VOLTAGE DROP PERCENT
$$ V_D\% = \frac{V_D}{V_{source}} \times 100 $$
NEC informational notes recommend ≤ 3% on branch circuits and ≤ 5% on the combined feeder + branch. Motors and electronics often need tighter limits.

Reference

NEC Table 310.16 — copper ampacity (75 °C, 3 conductors, 30 °C ambient)
AWGDiameter (in)Ampacity
140.06420 A *
120.08125 A *
100.10235 A *
80.12950 A
60.16265 A
40.20485 A
20.258115 A
10.289130 A
1/00.325150 A

* Branch-circuit breakers limited per 240.4(D) to 15 A (14), 20 A (12), 30 A (10).

Circular mil area for voltage-drop math
AWGCircular milsAluminum ampacity
144,107
126,53020 A
1010,38330 A
816,51040 A
626,24050 A
441,74065 A
266,36090 A
183,690100 A
1/0105,600120 A
Quick reference: copper wire size by load and one-way length (120 V, 3% voltage drop, 30 °C)
Load25 ft50 ft100 ft150 ft200 ft
15 A14 AWG14 AWG12 AWG10 AWG10 AWG
20 A12 AWG12 AWG10 AWG8 AWG8 AWG
30 A10 AWG10 AWG8 AWG6 AWG6 AWG
40 A8 AWG8 AWG6 AWG4 AWG4 AWG
50 A8 AWG6 AWG6 AWG4 AWG3 AWG
100 A3 AWG3 AWG2 AWG1 AWG1/0 AWG

Article — Electrical Wire Size Calculator

The right electrical wire size for a 20 A circuit at 50 ft on 120 V copper is 12 AWG. Stretch the same circuit to 150 ft and you must upsize to 10 AWG — not because the wire cannot carry 20 A, but because 12 AWG would lose almost 6% of the supply voltage to line resistance, well over the NEC 3% recommendation. Wire sizing always solves two equations at once: enough current-handling capacity (ampacity) and a small enough voltage drop. The bigger of the two answers is what goes in the wall.

This article walks through both checks, the AWG numbering system, copper-versus-aluminum trade-offs, derating for ambient temperature and conductor count, and the mistakes that most often turn into chimney-style attic fires or motors that hum instead of run.

Electrical wire size basics

U.S. residential wiring uses the American Wire Gauge (AWG) system. The numbers run backwards from intuition: 14 AWG is the smallest common branch-circuit wire (about 0.064 in diameter); 1/0 AWG is roughly five times larger at 0.325 in. Each three-step jump in the AWG count roughly doubles the conductor's cross-sectional area — 10 AWG holds about double the copper of 13 AWG. Above 1 AWG the system switches to 1/0, 2/0, 3/0, 4/0, then to kcmil (thousand circular mils) for service entrances and feeders.

The National Electrical Code (NEC) sets the legal minimums. NFPA 70, the document containing the NEC, has been updated on a three-year cycle since 1897 and is adopted — with state amendments — in all 50 U.S. states. Two NEC sections do most of the work for wire sizing: Table 310.16 gives base ampacities, and Article 215 covers feeder voltage drop. Section 240.4(D) imposes a strict cap on small conductors: 14 AWG cannot be protected above a 15 A breaker, 12 AWG above 20 A, or 10 AWG above 30 A — regardless of what the temperature column allows.

Did you know

The AWG numbers come from the number of drawing-die passes used in the original 1857 standard. A 30 AWG wire was drawn through 30 successive dies, each slightly narrower than the last. The lower the number, the fewer reductions — and the thicker the wire. The math is purely historical, but the system stuck.

Ampacity: the heat side of wire sizing

Every conductor dissipates heat in proportion to the square of the current. Push too much through a wire and the insulation softens, melts, or chars; once charring starts, the resistance climbs and the failure runs away. Ampacity is the engineering shorthand for "current at which the conductor stays under its insulation rating in steady state."

NEC Table 310.16 publishes ampacities at three insulation temperatures — 60 °C, 75 °C, and 90 °C — each at a 30 °C (86 °F) ambient with three conductors in a raceway. For a 75 °C copper insulation (the most common THWN-2 spec): 14 AWG carries 20 A, 12 AWG 25 A, 10 AWG 35 A, 8 AWG 50 A, 6 AWG 65 A. For most residential terminations the 60 °C column applies because of NEC 110.14(C)'s termination cap: panel lugs and breakers below 100 A are rated 60 °C, so the wire still ends up limited to 15 A on 14 AWG and 20 A on 12 AWG.

The 125% continuous-load rule is not optional

NEC 210.20(A) requires the breaker (and wire) to be sized at 125% of any load running three or more hours continuously — lighting circuits, EV chargers, electric water heaters. A 16 A EV charger needs a 20 A breaker on 12 AWG, never 15 A on 14 AWG, even though the steady-state current is below the smaller wire's rating.

Voltage drop: the efficiency side

Voltage drop is the supply voltage lost along the round-trip path back from the load. The formula is V_D = 2 × K × I × L / CM — where K is the material resistance constant (12.9 for copper, 21.2 for aluminum, both in CM·Ω/ft), I is current, L is the one-way length in feet, and CM is the conductor area in circular mils. The factor of two captures the return path.

NEC doesn't outright mandate a voltage-drop limit, but two informational notes (210.19(A) and 215.2(A)(3)) recommend keeping branch-circuit drop under 3% and the combined feeder-plus-branch under 5%. The reasoning is practical: motors lose torque, incandescent lamps dim noticeably, and switching power supplies start hunting once supply voltage swings more than about 5%. A 240 V air-handler on 4% drop sees 230 V at the motor — the motor still starts, but draws more current to compensate, accelerating insulation aging.

  • 12 AWG copper, 20 A, 120 V, 50 ft (one-way) — 3.95% drop, fails the 3% recommendation
  • 10 AWG copper, 20 A, 120 V, 50 ft (one-way) — 2.48% drop, passes comfortably
  • 6 AWG copper, 50 A, 240 V, 75 ft (one-way) — 2.46% drop
  • 4 AWG aluminum, 50 A, 240 V, 150 ft — 3.81% drop, upsize to 2 AWG
  • 1/0 AWG copper, 100 A, 240 V, 200 ft — 2.04% drop
  • Doubling length — doubles voltage drop at the same gauge

Copper vs aluminum for wire sizing

Copper conducts about 60% better than aluminum by cross-section — or put the other way, an aluminum conductor needs roughly 60% more area to match a copper one of the same gauge. In NEC tables that lands as a roughly 80% ampacity ratio: aluminum 10 AWG carries 30 A where copper 10 AWG carries 35 A.

The price difference favours aluminum — sometimes by a factor of two to three on the spool — which is why service-entrance cables and large feeders are usually aluminum. But aluminum oxidizes at terminations. The oxide layer is non-conductive, so a poorly torqued aluminum lug develops a high-resistance contact that heats, expands, loosens further, and eventually arcs. The mid-1960s saw a wave of aluminum branch-circuit wiring in U.S. homes, followed by enough fires that NEC effectively banned aluminum below 4 AWG in residential work.

Did you know

The U.S. Consumer Product Safety Commission estimated in a 1974 study that homes wired with aluminum branch circuits between 1965 and 1973 were 55 times more likely to reach "fire hazard" conditions at a receptacle than homes wired in copper. The fix — AlCu-rated devices or copper pigtails — is still standard remediation in older houses.

Temperature and conduit derating

NEC Table 310.15(B)(1) reduces ampacity above 30 °C ambient. The corrections are steep: 0.94 at 35 °C, 0.88 at 40 °C, 0.82 at 45 °C, 0.75 at 50 °C, 0.58 above 55 °C. An uninsulated Arizona attic can reach 60–70 °C in summer, cutting 12 AWG's 25 A rating below 15 A.

Conductor-count derating in Table 310.15(C)(1) is similarly aggressive: four to six current-carrying conductors in a single raceway derate to 80%, seven to nine to 70%, ten to twenty to 50%. The neutral counts as a current-carrying conductor on most multi-wire branch circuits unless the load is purely linear. Direct-buried cables get a different set of derations and benefit from the soil's thermal mass.

Stacking the wrong derations gives wrong results

Temperature derating and conductor-count derating multiply. A 12 AWG circuit with four conductors in conduit at 45 °C drops to 25 A × 0.82 × 0.80 = 16.4 A — below the 20 A nameplate. Calculators that only apply one factor or the other will quietly undersize the wire.

Conduit fill is a separate limit

NEC Chapter 9 Table 1 caps conduit fill at 53% for one conductor, 31% for two, 40% for three or more — measured by cross-sectional area, not visual fullness. Calculators size the wire; fill must be confirmed independently before a permit inspector signs off.

Common electrical wire size mistakes

Treating the ampacity table as the final answer

The 75 °C column shows 12 AWG copper at 25 A. NEC 240.4(D) caps that wire at 20 A in branch-circuit protection — the same way 14 AWG caps at 15 A — regardless of insulation rating. The table is a starting number, not a license.

Ignoring voltage drop on detached structures

A 20 A circuit to a detached garage 200 ft from the house needs 8 AWG copper, not the 12 AWG the panel would suggest. The most common defect on rural inspections is undersized feeders to outbuildings, found only after a compressor or welder refuses to start.

  • 1.25 multiplier — applied to all continuous loads before wire sizing
  • 3% / 5% voltage drop — NEC-recommended limits, branch vs feeder + branch
  • 60 °C termination cap — applies to most residential breakers and lugs
  • Aluminum +1 to +2 sizes — over the copper choice for equal ampacity
  • 4 AWG minimum — for aluminum in residential branch circuits
  • 15 / 20 / 30 / 40 / 50 A — standard breaker steps to round up to

FAQ

12 AWG copper for runs up to about 100 ft on 120 V (stays under 3% voltage drop). For longer runs, upsize: 10 AWG for 100–180 ft, 8 AWG beyond. Aluminum needs to step up to 10 AWG even at short distances. NEC 240.4(D) caps a 20 A breaker at 12 AWG copper or 10 AWG aluminum, no matter what the temperature column allows.
6 AWG copper or 4 AWG aluminum for runs up to 50 ft on 240 V. Longer pulls need 4 AWG copper or 2 AWG aluminum. Common applications — electric range, dryer, hot tub, mid-size EV charger — almost always pair the 50 A breaker with 6/3 NM-B cable in residential work.
Resistance accumulates with length. The voltage-drop formula V_D = 2 × K × I × L / CM is proportional to length: doubling the run doubles the drop at the same gauge. NEC recommends keeping branch-circuit drop under 3%, so long runs force a larger conductor even when ampacity alone would accept the smaller one.
NEC Table 310.15(B)(1) reduces ampacity above 30 °C ambient. Multipliers: 0.94 at 35 °C, 0.88 at 40 °C, 0.82 at 45 °C, 0.75 at 50 °C, 0.58 above 55 °C. An attic running 50 °C cuts 12 AWG's nameplate 25 A down to 18.75 A — below the 20 A breaker it would normally feed.
Yes, for 4 AWG and larger — service entrances and large feeders are almost always aluminum. NEC effectively prohibits aluminum below 4 AWG in residential branch circuits because of oxidation problems at receptacle and switch terminations. If you go aluminum, use only AlCu-rated devices and an approved oxide inhibitor on every termination.
Voltage drop is the supply voltage lost to wire resistance along the round-trip path. The NEC recommends ≤ 3% on a branch circuit. Higher drops cause motors to lose torque, lamps to dim, and electronics to fail randomly. A 4% drop on a 240 V air-handler leaves 230 V at the motor — the motor draws extra current to compensate, accelerating insulation aging.
Almost always. A 20 A circuit to a detached structure 200 ft from the panel runs about 7.9% drop at 12 AWG on 120 V — you need 8 AWG. A 60 A subpanel feeder at 240 V over the same distance needs 4 AWG copper or 2 AWG aluminum. Voltage drop, not ampacity, controls the answer for long pulls.
Each current-carrying conductor adds heat to the bundle, and the conduit limits heat dissipation. NEC 310.15(C)(1) requires 80% derating for 4–6 conductors, 70% for 7–9, and 50% for 10–20. The neutral counts as a current-carrying conductor on most multi-wire branch circuits unless the load is purely linear — not on a circuit with LED dimmers or VFDs.
The temperature is the maximum the insulation can reach in steady-state operation. 60 °C insulation (TW, UF) is the oldest and lowest-rated; 75 °C (THW, THWN) is the modern residential standard; 90 °C (THHN, XHHW) gives the highest ampacity. NEC 110.14(C) caps most residential terminations to the 60 °C column for circuits below 100 A regardless of wire rating — the lug, not the wire, is the limit.
The breaker protects the wire. NEC 240.4(D) caps small-conductor breakers: 15 A on 14 AWG, 20 A on 12 AWG, 30 A on 10 AWG — copper, regardless of insulation. Standard breaker sizes are 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125 A. Round the load up to the next standard size, then confirm the wire ampacity covers it.