Passive House

The Passive House calculator estimates annual heating demand in kWh/(m²·yr) and peak heating load in W/m² from your building's floor area, envelope U-values, window performance, temperature difference and heat-recovery efficiency.

Nature ≤15 kWh/m²·yr Heat-recovery aware Pass / fail check
Rate this calculator

Passive House Energy Calculator

Heating demand, peak load and Passivhaus compliance

Instructions — Passive House

1

Enter the building envelope

Type in the conditioned floor area, the total opaque envelope area (walls, roof and floor) and the window area. These set how much surface loses heat.

2

Add U-values and climate

Give the average envelope U-value, the window U-value, the indoor-minus-outdoor temperature and the heating season length in hours. Lower U-values mean less heat escapes.

3

Read the verdict

The calculator returns annual heating demand and peak load, then shows a pass or fail against the Passive House thresholds of 15 kWh/m²·yr and 10 W/m².

Formulas

Transmission heat loss
$$Q_{trans} = \sum (U_i \times A_i) \times \Delta T \times t$$

Heat conducted through walls, roof, floor and windows. U is the thermal transmittance, A the area, ΔT the temperature difference and t the heating hours.

Ventilation loss with recovery
$$Q_{vent,net} = \dot{V} \times \rho \times c_p \times \Delta T \times t \times (1 - \eta_{HRV})$$

Air leaving the house carries heat. A heat-recovery unit returns a fraction η, so only the remainder is lost.

Annual heating demand
$$q_{heat} = \frac{Q_{trans} + Q_{vent,net} - Q_{gains}}{A_{cond}}$$

Net heating energy per square metre of conditioned floor. Solar and internal gains are subtracted before dividing by floor area.

Peak heating load
$$P_{peak} = \frac{(UA_{env} + UA_{vent,net}) \times \Delta T_{design}}{A_{cond}}$$

The power needed on the coldest design day. Passive House requires this to stay at or below 10 W/m².

Reference

The Passive House (Passivhaus) standard defines absolute energy targets rather than relative savings. Typical certified values are listed below.

  • Heating demand ≤ 15 kWh/(m²·yr)
  • Peak heating load ≤ 10 W/m²
  • Airtightness ≤ 0.6 ACH at 50 Pa
  • HRV efficiency ≥ 75% (PHI certified)
  • Window U-value ≤ 0.80 W/(m²·K)
  • Wall U-value ≤ 0.15 W/(m²·K)
  • Roof U-value ≤ 0.12 W/(m²·K)
  • Thermal bridge Ψ ≤ 0.01 W/(m·K)

A conventional house typically uses 70 to 120 kWh/(m²·yr) for heating, so a Passive House cuts heating energy by 75 to 90 percent.

Article — Passive House

Passive House calculator: heating demand and compliance

A passive house is a building that uses 15 kWh per square metre of floor area per year or less for space heating, with a peak heating load at or below 10 W/m². That is roughly 80 percent less heating energy than a typical new home. This calculator estimates both figures from your envelope U-values, window performance, climate and heat-recovery efficiency, then tells you whether the design clears the standard.

The Passivhaus standard was developed in Germany in the late 1980s by physicist Wolfgang Feist. It is not a brand of house or a list of products. It is a performance target backed by physics: build an envelope good enough, and the building stays comfortable with almost no active heating. More than 25,000 certified passive house buildings now operate across Europe.

What is a passive house?

A passive house keeps a stable, comfortable indoor climate using mostly the heat that is already inside it: sunlight through windows, body heat from occupants, and waste heat from appliances. Active heating handles only the small shortfall on the coldest days.

Five design principles make this possible. Continuous thick insulation wraps the whole building. Triple-glazed windows with insulated frames cut conductive loss while still letting solar heat in. Mechanical ventilation with heat recovery supplies fresh air without throwing warmth away. Thermal-bridge-free detailing keeps the insulation layer unbroken at every junction. And an airtight envelope, verified by a blower-door test, stops uncontrolled drafts.

Did you know

A certified passive house in central Europe can be kept warm through winter by the equivalent of a single hair dryer running per room. The 10 W/m² peak load limit means a 150 m² home needs only about 1.5 kW of heating power.

The passive house criteria

The Passive House Institute (PHI) sets three hard limits that a building must meet to be certified. Annual heating demand must not exceed 15 kWh/(m²·yr). Peak heating load must stay at or below 10 W/m². Airtightness must reach 0.6 air changes per hour or better at 50 pascals of pressure, measured by a blower-door test.

Alongside these, the design must hit component-level targets. Window U-values should be 0.80 W/(m²·K) or lower, wall U-values around 0.15, and roof U-values around 0.12. For comparison, a code-minimum wall in many regions sits near 0.30 to 0.50, meaning a passive house wall loses two to three times less heat per square metre.

  • Heating demand ≤ 15 kWh/(m²·yr)
  • Peak load ≤ 10 W/m²
  • Airtightness ≤ 0.6 ACH at 50 Pa
  • HRV recovery ≥ 75 percent
  • Windows ≤ 0.80 W/(m²·K)
  • Walls ≈ 0.15 W/(m²·K)
  • Roof ≈ 0.12 W/(m²·K)
  • Thermal bridges Ψ ≤ 0.01 W/(m·K)

How the passive house calculator works

The passive house calculator builds a steady-state heat balance for the heating season. It adds up the energy lost, subtracts the energy gained for free, and divides by floor area to get a demand figure in kWh/(m²·yr).

Transmission loss is the heat conducted through walls, roof, floor and windows. It is the sum of each element's U-value times its area, multiplied by the indoor-outdoor temperature difference and the number of heating hours. Ventilation loss is the heat carried out by stale air; the calculator applies your heat-recovery efficiency so only the unrecovered share counts. Solar gains through windows and internal gains from people and equipment are then subtracted.

Quick mental model
losses = transmission + ventilation demand = (losses − gains) / area
peak load = UA × ΔT / area target: demand ≤ 15, peak ≤ 10

The result is a planning-grade estimate. It captures the terms that dominate a real heat balance, but certification still requires the full Passive House Planning Package (PHPP), which models monthly weather, shading geometry and every thermal bridge.

Tip

If your result fails on heating demand, improving window U-value usually moves the number fastest, because windows combine a high U-value with a large temperature swing. If it fails on peak load, focus on airtightness and reducing the worst thermal bridges.

Heat recovery in a passive house

Mechanical ventilation with heat recovery is the component that makes the passive house maths work. Once an envelope is heavily insulated and airtight, ventilation becomes one of the largest remaining losses. A heat-recovery ventilator (HRV) passes outgoing warm air and incoming cold air through a counterflow exchanger, transferring 75 to 85 percent of the heat without mixing the two streams.

An HRV moves heat only. An ERV, or energy recovery ventilator, also transfers moisture, which matters in hot humid climates where you want to keep incoming air dry, and in very cold dry climates where you want to retain indoor humidity. PHI-certified units must recover at least 75 percent of the heat to count toward the standard.

Conventional home
~90 kWh/m²·yr
no heat recovery, leaky envelope
Passive house
≤15 kWh/m²·yr
80%+ heat recovery, airtight

Passive house by climate zone

The passive house concept adapts to local climate, though the way the targets apply changes. In cold and temperate climates the 15 kWh/(m²·yr) limit applies to space heating, and an HRV is essentially mandatory. Cities like Berlin, Warsaw, Toronto and Chicago fall here, with insulation often 20 to 30 cm thick.

In hot climates the limit applies to combined heating and cooling, and an ERV handles moisture. In hot humid regions like Miami or Houston the North American Phius CORE standard is generally used instead of the fixed PHI limit, because it sets climate-adjusted targets rather than one global number.

Overheating is a real risk

A passive house that is excellent at keeping heat in can also trap unwanted summer heat. Designs that pass the heating check can still overheat without external shading, careful window orientation and a free-cooling or night-purge ventilation mode. Always check the cooling and overheating frequency, not just the heating demand.

Passive house costs and payback

Building to the passive house standard typically adds 5 to 10 percent to construction cost, occasionally up to 20 percent where local trades lack experience. The extra spend goes into thicker insulation, better windows and the ventilation system.

That premium is recovered through lower energy bills. Payback periods of 3 to 7 years are common in regions with high energy prices, stretching to 5 to 10 years in mild climates with cheap energy. Because the insulation and windows last the life of the building, the savings continue for decades after the payback point.

Did you know

Over a 50-year life cycle, a passive house can cut total carbon emissions by around 40 percent compared with a conventional home of the same size, even after accounting for the extra embodied carbon in insulation and glazing.

Common passive house mistakes

The most frequent design error is treating the passive house standard as an insulation problem alone. Thick walls help, but uncontrolled air leakage and thermal bridges can quietly destroy the heat balance. A single poorly detailed balcony slab or window reveal can add measurable load.

A second mistake is ignoring the blower-door test until late. Airtightness has to be designed in and verified during construction, ideally once when the airtight membrane is complete and again at handover. Retrofitting airtightness into a finished building is slow and expensive. Finally, oversizing windows on the wrong orientations boosts winter loss and summer overheating at the same time, so glazing should be planned alongside shading from the start.

FAQ

A building qualifies as a Passive House when its annual space heating demand is 15 kWh per square metre of treated floor area per year or less, and its peak heating load is 10 W/m² or less. These are absolute physical limits set by the Passive House Institute, not relative savings targets. A typical new conventional house uses 70 to 120 kWh/(m²·yr) for heating, so the standard represents a reduction of roughly 80 percent.
This tool gives a fast planning estimate using simplified steady-state heat balance formulas based on ISO 13790. It captures the dominant terms: transmission loss, ventilation loss after heat recovery, and solar and internal gains. Official certification still requires the full Passive House Planning Package (PHPP), which models monthly weather data, shading, thermal bridges and climate-specific factors that a quick estimate cannot reproduce.
In a well-insulated airtight house, ventilation becomes one of the largest remaining heat losses. A mechanical ventilation unit with heat recovery (HRV) or energy recovery (ERV) transfers 75 to 85 percent of the heat from outgoing stale air to incoming fresh air. Without recovery, that heat would simply be exhausted, and meeting the 15 kWh/(m²·yr) target would be nearly impossible in a cold climate.
Yes. In hot climates the 15 kWh/(m²·yr) limit applies to combined heating and cooling, and an ERV is used to recover moisture as well as heat. In hot humid regions the North American Phius CORE standard, which adjusts targets by climate zone, is often used instead of the fixed PHI limit.
U-value measures how readily heat passes through a building element, in W/(m²·K). A lower U-value means better insulation. R-value measures thermal resistance and is the inverse: a higher R-value is better. This calculator uses U-values because heat loss scales directly with U times area times temperature difference.
It needs one, but a very small one. Because peak load stays at or below 10 W/m², a 150 m² Passive House needs only about 1.5 kW of heating power, often delivered by a small heat pump or a post-heater on the ventilation supply air. That is a fraction of the 5 to 15 kW boiler a conventional house of the same size would require.