kVA Calculator (Apparent Power, 1-Phase & 3-Phase)

Calculate apparent power in kilovolt-amperes (kVA) from voltage and current.

Science 1Ø or 3Ø Real & reactive power Phase angle φ
Rate this calculator · 4.0 (2)

kVA from volts and amps

Single-phase or three-phase · power factor adjustable

Instructions — kVA Calculator (Apparent Power, 1-Phase & 3-Phase)

  1. Select 1-phase (residential, light commercial) or 3-phase (industrial, generators above ~5 kVA).
  2. Enter voltage in volts. Common picks: 120 V (US single-phase), 230 V (EU single-phase), 400 V (EU 3Ø), 480 V (US 3Ø).
  3. Enter current in amperes drawn by the load.
  4. Enter the power factor (cos φ). Typical values: 0.95–1.0 lighting, 0.85–0.92 induction motors, 0.7–0.8 welders.
  5. Read apparent power (kVA), real power (kW), reactive power (kVAR), and phase angle.

kVA is what the utility delivers; kW is the useful work. The gap is reactive power, which oscillates between source and load without doing work.

Formulas

Single-phase: S = V × I / 1000
Three-phase: S = √3 × V × I / 1000

Power decomposition

P (kW) = S × cos φ
Q (kVAR) = S × sin φ = S × √(1 − cos²φ)

Where

  • S — apparent power (kVA)
  • V — line-to-line voltage for 3Ø; phase voltage for 1Ø
  • I — line current (A)
  • cos φ — power factor (dimensionless, 0 to 1)
  • √3 ≈ 1.7320508 — geometric factor from 120° phase offset

Worked example

A 3-phase induction motor draws 25 A at 400 V with a 0.88 power factor. S = √3 × 400 × 25 / 1000 = 17.32 kVA. P = 17.32 × 0.88 = 15.24 kW. Q = 17.32 × √(1 − 0.88²) = 8.24 kVAR.

Reference

Common voltages

SystemVoltagePhase
US household120 V / 240 V1Ø (split)
European household230 V
US light commercial208 V
European industrial400 V
US industrial480 V
Heavy industrial4.16 kV / 13.8 kV

Typical power factors

  • Incandescent lamps, resistive heaters: 1.0
  • LED lighting (good driver): 0.95–1.0
  • Computers, electronics: 0.6–0.95
  • Induction motors at full load: 0.85–0.92
  • Induction motors at light load: 0.4–0.6
  • Arc welders: 0.5–0.7
  • HID lighting: 0.40–0.90 depending on ballast

Sizing rule of thumb

Add a 20–25 % safety margin when picking a generator or transformer. A 15 kW load at 0.85 pf needs 15 / 0.85 = 17.6 kVA; size the generator to 22 kVA.

Article — kVA Calculator (Apparent Power, 1-Phase & 3-Phase)

kVA calculator — convert volts and amps to apparent power

kVA stands for kilovolt-ampere, the unit of apparent power. For a single-phase circuit, kVA = V × I ÷ 1000. For a balanced three-phase system, kVA = √3 × V × I ÷ 1000, where V is the line-to-line voltage and I is the line current. The 1.732 multiplier comes from the geometric sum of three currents that are 120 degrees apart in time.

Apparent power is what the utility actually delivers through the wires. Some of that power does work (kW); some bounces back and forth between source and load without doing anything useful (kVAR). The ratio between real and apparent power is the power factor, and it sits at the heart of every kVA calculation.

What is kVA?

kVA is apparent power — the product of root-mean-square voltage and current in a circuit, divided by 1000 to convert volt-amperes to kilovolt-amperes. It captures the total electrical loading on the wires, transformer, and generator, regardless of how efficiently the load converts that energy into useful work.

A 100 kVA transformer can supply up to 100,000 volt-amperes simultaneously. Whether the load uses all of that as real work (a heater bank, power factor 1.0) or wastes some as circulating reactive power (an induction motor, power factor 0.85) does not change the apparent power demand on the transformer windings.

Did you know

Utilities size every transformer, substation, and generator in kVA — never in kW. The reason is simple: a transformer's windings heat up from current, regardless of phase angle. A 500 kVA transformer can carry 500,000 VA whether the load runs at unity power factor or 0.7.

kVA formula for single-phase and three-phase

The single-phase formula is the simpler case: multiply the line voltage by the line current and divide by 1000. For a US household running at 240 V and drawing 100 A, that is 240 × 100 ÷ 1000 = 24 kVA peak demand.

kVA formulas at a glance
1-phase kVA = V × I / 1000
3-phase kVA = √3 × V × I / 1000
From kW kVA = kW / cos φ
To amps (1Ø) I = kVA × 1000 / V
To amps (3Ø) I = kVA × 1000 / (√3 × V)

The three-phase formula uses line-to-line voltage and the per-phase line current. A factory motor branch at 480 V drawing 50 A per phase pulls 1.732 × 480 × 50 ÷ 1000 = 41.6 kVA. Real power depends on the motor's power factor, typically around 0.88 at full load, so the same circuit delivers about 36.6 kW of mechanical work.

kVA vs kW vs kVAR — three flavors of power

Real power (kW) is what does work — heat, motion, light. Reactive power (kVAR) is the energy that oscillates between the source and inductive components like motor windings or transformer cores. Apparent power (kVA) is the vector sum of the two, and it is what the wires actually carry.

Real power
kW
Does the work
Reactive
kVAR
Bounces back
Apparent
kVA
Total on wires

The three are related by the power triangle: kVA² = kW² + kVAR². A 10 kW motor with 5 kVAR of reactive demand has an apparent power of √(100 + 25) = 11.2 kVA. The 1.2 kVA gap is wasted from the utility's perspective and shows up on the bill of large customers as a power-factor penalty.

Power factor and why it matters

Power factor is cos φ — the cosine of the phase angle between voltage and current waveforms. A purely resistive load (heater, incandescent bulb) has power factor 1.0; voltage and current peak together. An inductive load (motor, transformer) pulls current that lags voltage, dropping power factor below 1. Capacitive loads (some electronics, capacitor banks) push current to lead voltage and bring power factor back up.

Tip

Power factor correction with capacitor banks usually pays back in 18–36 months for industrial sites. Adding 100 kVAR of capacitance to a plant running at 0.8 pf can raise it to 0.95+, cut line losses by 10–15 %, and erase utility penalties altogether.

Generator and transformer sizing in kVA

Always specify generators and transformers in kVA, not kW. The kW rating is load-dependent; the kVA rating is what the equipment can physically supply. Standard practice adds a 20–25 % safety margin to handle motor inrush current (which can spike to six times the running current for 50–200 milliseconds during startup).

  • Residential standby = 10–22 kVA covers a typical US home with central air conditioning.
  • Small commercial = 50–150 kVA powers a restaurant, dental office, or small retail unit.
  • Mid-size building = 250–1000 kVA serves a mid-rise office, hospital wing, or warehouse.
  • Data center pod = 1500–3000 kVA per UPS module, with N+1 redundancy.
  • Utility substation = 10,000+ kVA (10 MVA) per transformer, multiple per site.
  • EV fast charger = 50–350 kVA per stall, 3-phase 400/480 V.

Typical kVA by appliance and building

A 230 V single-phase electric kettle pulls about 2 kW at unity power factor — call it 2 kVA. A 1.5 hp pool pump motor running 230 V single-phase at 0.85 power factor needs roughly 1.3 kVA. A 50 hp three-phase industrial motor at 460 V draws around 47 kVA at full load. Scale the numbers and you can spot-check any installation against its main feeder.

Why three-phase uses the √3 factor

Three-phase power uses three separate conductors carrying alternating currents offset by 120 degrees in time. At any instant, the sum of the three instantaneous currents is zero (in a balanced system), but the average power delivered is √3 times what a single phase at the same line-to-line voltage and current would deliver. The 1.732 multiplier is the geometric resolution of three balanced phasors.

! Watch the voltage definition

In a 3-phase formula, V is the line-to-line voltage (e.g., 400 V or 480 V), not the phase-to-neutral voltage. Mixing them is the most common mistake — using 230 V (phase voltage) instead of 400 V (line voltage) in a European 3-phase formula undersizes the result by √3.

Common kVA calculation mistakes

Three patterns show up repeatedly. First, applying the single-phase formula to a three-phase circuit and missing the √3 factor — instant 73 % undersize. Second, confusing kW load with kVA capacity when sizing generators, leading to overload tripping when motors start. Third, ignoring power factor entirely and assuming 1.0 for an inductive load — guarantees a generator runs out of headroom and stalls under real load.

FAQ

kVA (kilovolt-amperes) is apparent power — what the utility supplies. kW (kilowatts) is real power — what does work. The relationship is kW = kVA × power factor. For a pure resistive load (heater, incandescent bulb) the two are equal; for motors and electronics they diverge.
In a balanced 3-phase system, the three currents are 120° apart in time. The vector sum of the per-phase power gives √3 × V_line × I_line. Geometrically it is the diagonal of the three balanced phasors.
Single-phase: I = (kVA × 1000) / V. Three-phase: I = (kVA × 1000) / (√3 × V). A 100 kVA three-phase transformer at 400 V delivers 100,000 / (1.732 × 400) ≈ 144 amps per phase.
0.8 is the standard default for sizing generators and transformers per most electrical codes. Pure resistive loads use 1.0. Use 0.85 for mixed industrial loads, 0.9 for modern office/data center loads.
A typical US single-family home draws 100–200 A at 240 V, which is 24–48 kVA peak. The averaged demand is much lower — usually 1.5–3 kVA continuous. Generator sizing uses peak; utility billing uses kWh.
Only if the power factor is 1.0, which is never true for a motor. A 5 kW motor at 0.85 pf needs 5 / 0.85 = 5.88 kVA. Always size the generator above the load kVA, with margin for startup surge.
Motors are rated by mechanical output power (kW). Generators are rated by what they can supply electrically (kVA), independent of the load's power factor. The two ratings are not directly interchangeable without knowing pf.
Utilities often charge a penalty when pf drops below 0.95. Adding capacitors near inductive loads cancels reactive power locally, raises pf toward 1.0, reduces line losses, and often unlocks a 5–15 % electricity bill cut for industrial users.