Wire Resistance Calculator

Compute the resistance of a wire from its material, length, and cross-section.

Science 6 materials AWG · mm² · diameter
Rate this calculator · 5.0 (1)

Wire resistance

R = ρ · L ÷ A

Instructions — Wire Resistance Calculator

Pick a conductor material, choose how you want to specify the wire size, and enter the wire length. The calculator computes resistance using R = ρL/A, applies a temperature correction with the material's α coefficient, and optionally reports voltage drop and power loss if you supply a current.

  1. Choose material — copper, aluminum, silver, gold, tungsten, or nichrome. Each has the standard ρ at 20°C and temperature coefficient α built in.
  2. Choose size mode — AWG gauge (US standard), cross-section in mm² (metric), or diameter in mm.
  3. Enter length and temperature — length in metres or feet, temperature in °C (defaults to 20°C, the reference).
  4. Add current (optional) — supply amperes to see the voltage drop (V = IR) and power loss (P = I²R).

Formulas

Wire resistance: R = ρ · L ÷ A

AWG to diameter: d[mm] = 0.127 · 92^((36 − AWG) ÷ 39)

Diameter to area: A = π · (d ÷ 2)²

Temperature correction: R(T) = R₀ · [1 + α · (T − 20)] with T in °C.

Voltage drop and power loss: V_drop = I · R, P_loss = I² · R.

Conductivity: σ = 1 ÷ ρ — copper σ ≈ 5.96 × 10⁷ S/m.

Reference

Material resistivity at 20°C (Ω·m). Silver 1.59 × 10⁻⁸, copper 1.68 × 10⁻⁸, gold 2.44 × 10⁻⁸, aluminum 2.65 × 10⁻⁸, tungsten 5.5 × 10⁻⁸, nichrome 1.1 × 10⁻⁶. Copper's combination of low ρ, ductility, and price keeps it the universal default for household and industrial wiring.

AWG shortcut. Every 3-step AWG change roughly halves or doubles the cross-section. AWG 14 (2.08 mm²) carries 15 A in residential US code; AWG 12 (3.31 mm²) carries 20 A; AWG 10 (5.26 mm²) carries 30 A.

Length is the round trip. For a circuit with separate hot and neutral wires, total resistance counts both legs. Always double the one-way distance when sizing for voltage drop.

Article — Wire Resistance Calculator

Wire resistance calculator: sizing conductors right

Wire resistance is the opposition a conductor offers to current flow. It follows R = ρL/A — resistivity times length over cross-section area. Copper at 20°C has ρ = 1.68 × 10⁻⁸ Ω·m, so a 10 m run of 2 mm² copper has R ≈ 0.084 Ω. Resistance rises with length, falls with cross-section, and grows roughly 0.4% per °C of temperature increase.

Every wire wastes some electrical energy as heat. That waste shows up as a voltage drop along the wire (V = IR) and as power loss inside it (P = I²R). For a household circuit, those numbers are usually small. For a 200 m underground feed to a workshop, they can decide whether your motor starts or just hums.

What is wire resistance?

Wire resistance comes from electrons scattering off the lattice of metal ions as they drift through a conductor. The longer the path, the more scattering events; the wider the path, the more parallel routes for current to spread across. Both effects show up in the simple geometric formula R = ρL/A.

Resistivity ρ is the material property — how much a unit cube of that metal opposes current. Resistance R is the property of a specific wire — what ρ becomes when you stretch it to a real length and shrink it to a real cross-section. Conductivity σ = 1/ρ is the reciprocal, often more convenient when comparing "how well does this material carry current".

Did you know

Silver has the lowest resistivity of any common metal — 1.59 × 10⁻⁸ Ω·m, just 5% less than copper. But silver costs more than 100× as much. That's why copper is the standard for electrical wiring, with silver reserved for high-grade contacts, audio terminals, and specialty switchgear.

The wire resistance formula

The full set of formulas needed to size a real conductor:

Wire resistance and related formulas
Resistance R = ρ · L ÷ A
AWG to mm d = 0.127 · 92^((36 − AWG)/39)
Area from diameter A = π · (d/2)²
Temperature R(T) = R₀ · [1 + α(T − 20)]
Voltage drop V_drop = I · R
Power loss P = I² · R

Units have to match. Plug ρ in Ω·m, L in metres, and A in square metres for the standard equation. If you have A in mm², multiply by 10⁻⁶ to convert. The calculator handles all conversions internally, but you'll want to know the formula for sanity checks.

Wire resistance by material

Resistivity at 20°C for common materials, with notes on where each is used:

  • Silver 1.59 × 10⁻⁸ Ω·m — premium contacts, antennas.
  • Copper 1.68 × 10⁻⁸ Ω·m — universal default for wiring.
  • Gold 2.44 × 10⁻⁸ Ω·m — connectors, corrosion-resistant contacts.
  • Aluminum 2.65 × 10⁻⁸ Ω·m — overhead transmission lines, building feeders.
  • Tungsten 5.5 × 10⁻⁸ Ω·m — incandescent filaments, electron tubes.
  • Nichrome 1.1 × 10⁻⁶ Ω·m — heating elements (65× copper's resistivity).
  • Constantan 4.9 × 10⁻⁷ Ω·m — precision resistors (α ≈ 0).
  • Stainless steel 6.9 × 10⁻⁷ Ω·m — heating elements in harsh environments.

Copper wins by being inexpensive, ductile, corrosion-resistant, and well-understood after a century and a half of mass use. Aluminum is roughly 60% the conductivity but a third the weight, which makes it the default for utility-scale transmission where wire weight matters more than connection complications.

AWG versus mm² sizing

North America uses American Wire Gauge; most of the rest of the world uses mm² cross-section. The conversion is logarithmic — every 3-step change in AWG roughly halves the area. Conversions for common sizes:

AWG 12
US standard outlet
3.31 mm²
20 A circuit, 2.05 mm diameter
AWG 6
Heavy appliance
13.3 mm²
55–65 A, 4.12 mm diameter
  • AWG 14 ≈ 2.08 mm² — 15 A residential circuits.
  • AWG 12 ≈ 3.31 mm² — 20 A receptacles.
  • AWG 10 ≈ 5.26 mm² — 30 A appliances.
  • AWG 8 ≈ 8.37 mm² — 40–50 A circuits.
  • AWG 6 ≈ 13.3 mm² — 55–65 A subpanels.
  • AWG 4 ≈ 21.2 mm² — 70–85 A feeders.
  • AWG 1/0 ≈ 53.5 mm² — 150 A residential service.

Voltage drop and wire resistance

The same physics that limits wire resistance limits how far you can run a circuit before the voltage drop becomes unacceptable. Residential code typically allows 3% drop; commercial 5%. The standard rule: V_drop = I · R, but R has to include both legs of the circuit (out and back).

Worked example: 30 m run feeding a 30 A circuit at 240 V, looking for under 3% drop (7.2 V max). Round trip is 60 m. R_max = V_drop / I = 7.2 / 30 = 0.24 Ω. Needed area: A = ρL / R = 1.68 × 10⁻⁸ × 60 / 0.24 = 4.2 × 10⁻⁶ m² = 4.2 mm². AWG 10 (5.26 mm²) just clears it; AWG 8 gives margin.

Always count both legs

A 30 m feeder runs out 30 m and back 30 m, so the total wire length for resistance is 60 m. Calculating with only 30 m halves the resistance and doubles the apparent capacity — leading to undersized conductors that overheat under load.

Temperature effects on wire resistance

Resistance rises linearly with temperature: R(T) = R₀ · [1 + α(T − 20°C)]. The temperature coefficient α depends on the metal. Copper sits at 0.00393/°C — about 0.4% per degree.

The effect is bigger than people expect. A 10 Ω copper coil at 20°C climbs to 12.4 Ω at 80°C — a 24% increase. For heating elements, that's a built-in current limiter: as the element heats up, resistance rises, current drops, heat output stabilises. Constantan and Manganin are alloys deliberately formulated to have near-zero α, which makes them the materials of choice for precision resistors and shunts where temperature stability matters.

Tip

When designing for a long-duration high-current load, derate the wire size by the temperature factor. A wire that sees 50°C continuous (above 20°C reference) carries roughly 12% more resistance and dissipates 12% more heat as I²R loss. Codes account for this implicitly through conduit-fill and ampacity tables.

Common wire-resistance mistakes

Six errors that trip up DIY electricians and sometimes professionals:

  • Sizing by ampacity only — passes code on amperage but fails on voltage drop for long runs.
  • Forgetting the round trip — total wire length is twice the one-way distance.
  • Mixing AWG and mm² incorrectly — AWG 12 is 3.31 mm², not 12 mm².
  • Ignoring temperature derating — wires in conduit, attics, or sun-exposed sites need bigger sizes.
  • Aluminium without proper terminations — Al oxidises; use rated lugs and antioxidant compound.
  • Skin effect at high frequency — at 50/60 Hz it's negligible, but past a few hundred kHz the effective conductor area shrinks and resistance rises.
Did you know

Superconductors have exactly zero resistance below their critical temperature. The first one discovered was mercury, in 1911, with T_c = 4.2 K. Today's high-temperature ceramic superconductors work above liquid nitrogen temperature (77 K), enabling MRI magnets, particle accelerators, and experimental power transmission cables.

FAQ

Use R = ρ · L / A, where ρ is the resistivity of the conductor (Ω·m), L is the length (m), and A is the cross-sectional area (m²). For copper at 20°C, ρ = 1.68 × 10⁻⁸ Ω·m. A 10 m run of 2 mm² copper has resistance R = 1.68 × 10⁻⁸ × 10 / 2 × 10⁻⁶ = 0.084 Ω.
Aluminum has about 1.6× higher resistivity, so the same resistance needs 1.6× larger cross-section. Aluminum is 3× lighter and cheaper, which is why utility transmission lines use it. Copper is the standard for home wiring because of its stability, corrosion resistance, and lower contact issues at terminals.
American Wire Gauge is a logarithmic sizing system: smaller numbers are thicker wires. Each 3-step change roughly halves the cross-section. Common conversions: AWG 14 ≈ 2.08 mm², AWG 12 ≈ 3.31 mm², AWG 10 ≈ 5.26 mm², AWG 8 ≈ 8.37 mm², AWG 6 ≈ 13.3 mm².
Resistance rises linearly: R(T) = R₀ · [1 + α(T − 20°C)]. Copper's α is 0.00393/°C — about 0.4% per degree. A copper wire that's 10 Ω at 20°C becomes 12.4 Ω at 80°C, a 24% increase. Heating elements exploit this for self-regulation.
Three checks: (1) ampacity — the wire must handle peak current without overheating; (2) voltage drop — keep drop below 3% residential or 5% commercial: V_drop = I · R; (3) code compliance — local electrical codes set minimum sizes for specific circuits. Always round up to the next standard gauge.
Resistivity ρ is an intrinsic material property measured in Ω·m. It tells you how much a 1 m × 1 m² block of material resists current. Resistance R of a specific wire depends on resistivity plus geometry (R = ρL/A). Conductivity σ = 1/ρ is the reciprocal — easier to use when comparing how well materials carry current.
Joule heating: P = I² · R. Every watt of dissipated power becomes heat. A 20 A current through 0.1 Ω of wire dissipates 40 W — enough to melt insulation if the wire is undersized. This is why ampacity ratings exist.